CHAPTER 2
p. 31
CHAPTER 2 CIRCUIT PROTECTION AND DISTRIBUTION The first chapter of this module dealt with the various devices used to provide electrical power in naval aircraft. This chapter discusses the different methods used to regulate the output voltages and frequencies of ac generators, through controls, circuit protection, and distribution systems. CONTROLS AND REGULATION LEARNING OBJECTIVES : Identify alter- nating current (ac) generator controls. Describe ac generator voltage regulation. Describe ac generator frequency control. Methods of voltage regulation include varying the current to the generator exciter windings and maintaining a constant load on the generator. This is accomplished by using a voltage regulator. Generator output frequency is regulated by keeping the generator rotating at a required speed. This is done by mounting the generator on a constant speed drive (CSD) unit. The most common method of voltage control in power generating systems is varying the current to the generator exciter winding (sometimes called field winding). This, in turn, changes the size of the magnetic field, which changes the voltage output of the generator. The second method of voltage regulation is to maintain a constant load on the generator. This method uses a permanent magnet on the generator rotor in place of exciter windings, which simplifies generator construction. This type of regulation must be used with systems that supply constant loads and have a limited capacity. For example, an inverter or an electronic power supply uses this type of voltage regulation. The regulator varies the resistance of a parallel resistor, so total resistance remains constant regardless of the load resistance. This type regulator is for use with both ac and direct current (dc) power sources. AC GENERATOR VOLTAGE CONTROL When magnetic fields of alternating polarity pass across the armature windings, ac voltage induction occurs. Control of the voltage induced into the ac generator windings depends on three things: • The number of turns of conductor per winding • The speed of the magnetic field passing across the winding (generator revolutions per minute [rpm]) • The magnetic field strength The number of turns per winding and the number of windings are set during generator manufacture. The frequency of the output voltage depends on the speed of the generator. The strength of the magnetic field controls the level of output voltage. In some cases, as in tachometer generators, a permanent magnet field maintains the load at a constant value. In today’s aircraft, electrical and electronic equipment operate at exact frequencies and voltages. Systems exposed to extreme overvoltages or off-frequencies not only destroy themselves, but may start a fire during an emergency. Ac generator control systems must contain circuits to protect against undervoltage and overvoltage, underfrequency and overfrequency, and improper phase sequence. The generators shown in figure 2-1(A) and 2-1(B) use an electromagnetic field rather than a permanent magnet-type field. NOTE: Some brushless generators use permanent magnets in the exciter circuits. The current flowing through the field controls electromagnetic field strength. To control the field strength, you vary the voltage applied across the field. By varying the dc output voltage from the exciter armature, you control the ac generator field strength. The value of the generated ac voltage depends directly on the size of the exciter input. This relationship allows a small dc voltage to control a much larger ac voltage. On the brushless generator, the rotating three-phase rectifiers change the ac output of the exciter to dc. Dc then feeds the main ac generator rotating field, eliminating the use of brushes. 2-1
p. 32
AC GENERATOR VOLTAGE REGULATION As you have already learned, controlling the strength of the magnetic field controls the generated voltage. A voltage regulator controls the magnetic field strength. Current generating the magnetic field is known asexcitation current. The auxiliary dc generator (called the exciter) or a rotating three-phase rectified ac exciter generator supplies this current. The exciter is on the same shaft as the ac generator to make it an integral part of the generator. The military specification for aircraft ac generators states that they should be self-supporting. To meet this requirement, dc exciter units are integrated into the ac generators. The chief advantage of exciter units is that each generator has its own independent source of excitation. No external source of electric power is necessary for generator operation. In a multi-generator installation, failure of one generator exciter does not make the complete system inoperative. This would happen if a generator system had a common external excitation system. Internal excitation makes it unnecessary to transmit excitation power, which reduces the chances of losing excitation from an open or short-circuited wire. In contrast to dc generators, the magnetic field coils in most aircraft ac generators rotate. This induces the ac voltage into the stationary windings. Reference Voltage Regulator One type of voltage regulator that has no mechanical moving parts (except the exciter control relay) is the solid-state regulator. The ac generator output flows to the voltage regulator, which compares it to a reference voltage. The difference supplies the control amplifier section of the regulator (fig. 2-2). If the output is too low, regulator circuitry increases the field strength of the ac exciter. If the output is too high, it reduces the field strength. The power supply for the bridge circuit is CR1. CR1 provides full-wave rectification of the three-phase output from transformer T1. The dc output voltages of CR1 are proportional to the average phase voltages. 2-2 TO VOLTAGE REGULATOR AND AC BUS TT FF11 2 2 AC ARMATURE EXCITER EXCITER ARMATURE ROTATING AC FIELD SINGLE PHASE AC GENERATOR T3 T4 T1 E2 E3 E1 EXCITER FIELD PILOT EXCITER (OUTPUT GOES TO VOLTAGE REGULATOR) T6 T5 MAIN AC GENERATOR MAIN AC GENERATOR ROTATING FIELD PILOT EXCITER ROTATING FIELD ROTATING PORTION EXCITER ARMATURE THREE-PHASE BRIDGE RECTIFIER T2 F S A A B AEf02001 STABILIZING FIELD INPUT FROM VOLTAGE REGULATOR Figure 2-1.—Ac generators. (A) brush type; (B) brushless type. ( ) ( )
p. 33
The negative anode of CR1 supplies power through point B, R2, point C, Zener diode CR1, point D, and to parallel-connected V1 and R1. Takeoff point C of the bridge is located between resistor R2 and the Zener diode. The other leg of the reference bridge (resistors R9, R7, and temperature compensating resistor RT1) connects in series with V1 and R1 through points B, A, and D. The output of this leg of the bridge is at point E. As voltage changes occur, voltage across R1 and V1 (once V1 starts conducting) remains constant, leaving the total voltage change occurring across the bridge. Since voltage across the Zener diode remains constant (once it starts conducting), the total voltage change occurring in that leg of the bridge is across resistor R2. In the other leg of the bridge, the voltage change across the resistors is proportional to their resistance values. For this reason, the voltage change across R2 is greater than the voltage change at point E. If the generator output voltage drops, point C is negative with respect to point E. Conversely, if the generator voltage output increases, the voltage between the two points reverses polarity. The bridge output taken between points C and E connects between the emitter and the base of transistor Q1. With the generator output voltage low, the voltage from the bridge is negative to the emitter and positive to the base. This is a forward bias signal to the transistor, and the emitter to collector current increases. With the increase of current, the voltage across emitter resistor R11 increases. This increase, in turn, applies a positive signal to the base of transistor Q4, which increases emitter to collector current and increases the voltage drop across emitter resistor R10. This gives a positive bias on the base of Q2, which increases its emitter to collector current and increases the voltage drop across its emitter resistor, R4. This positive signal controls output transistor Q3. The positive signal on the base of Q3 increases the emitter to collector current. The control field of the exciter generator is in the collector circuit. Increasing the output of the exciter generator increases the field strength of the ac generator, which increases the generator output. An underspeed switch located near the F+ terminal prevents generator excitation when the frequency is at a low value. When the generator reaches a suitable operating frequency, the switch closes and allows the generator excitation. Resistors R27, R28, and R29 connect in series with the normally closed contacts of relay K1. The coil of relay K1 connects across the power supply (CR4) for the transistor amplifier. When the generator starts turning, electricity from the 28-volt dc bus goes to the exciter generator field to flash the field for initial excitation. When the field of the exciter generator energizes and the ac generator output voltage increases, relay K1 energizes, opening the field flash circuit. 2-3 CR1 R1 V1 E RT1 R7 R9 R2 C CR5 R29 R28 R27 K1 N +2 8V UNDERSPEED SWITCH F+ A+ A- AC GENERATOR EXCITER CR2 CR3 Q3Q2Q4Q1 R6 R3 R8 A B D CR1 CR4 CR4 T3 T2 N T1 T1 F A R GK1 Y GENERATOR NEGATIVE BUS R11 R10 R4 AEf02002 Figure 2-2.—Solid-state voltage regulator.
p. 34
Sensing Voltage Regulator Another type of solid-state voltage regulator (fig. 2-3) operates by sensing the voltage existing on the lines. It amplifies the changes in this signal, and varies the average current supplied to the field winding of the integral exciter. The voltage regulator consists of a sensing circuit with input rectifiers, a tempera- ture compensated Zener diode, reference and error-detecting bridge, and a three-stage transistor amplifier. The output of the bridge circuit is a voltage inversely proportional to the difference between generator voltage and regulator set voltage. This output is referred to as the error signal. Transformer T1 in the regulator supplies three-phase, ac generator output. It provides isolation from the generator and delivers correct utilization voltages. The transformer output passes through the full-wave bridge rectifier (CR1) to obtain a dc voltage to supply the comparison circuit. The rectifier output is proportional to the average of the three line voltages. The voltage reference and error-detecting bridge uses this voltage for comparison with the constant voltage across the Zener diode (CR5), which tells whether the generator output is too high or too low. Potentiometer R7 permits adjustment to the desired voltage. The glow tube (V1) serves to increase the sensitivity of the voltage reference and error-detecting bridge. Thermistor RT1 provides temperature compensation in the comparison circuit. It offsets the effects of changes in other elements of the circuit that result from temperature variations to maintain a nearly constant voltage. The error-detecting bridge output voltage sawtooth wave shape is due to the ripple resulting from the semi-filtered, three-phase rectifier supply. This sawtooth voltage goes to the input of the first stage of the three-stage transistor amplifier. Overdriving the second and third stages obtains an essentially square wave output. The effect of the error detecting bridge output is to modulate the width of the pulses passing through the amplifier. Refer to figure 2-3 as you read this paragraph. The power for operating the three-stage transistor amplifier comes through the full-wave bridge rectifier (CR4) from transformer T1. Obtaining amplifier power this way requires special consideration. There are con- ditions that require excitation when no voltage is available to supply the amplifier. Such conditions exist 2-4 CR4+ - V1 RT1 R7 POT CR5 95-103V. CR1 K1 RELAY COIL K 1 RELAY CONTACTS + - 0 0 0 0 0 0 A B C A B C 0 0 0 A B C AEf02003 Figure 2-3.—Solid-state voltage regulator schematic.
p. 35
during initial buildup of system voltage and during three-phase short circuit on the generator. Control relay (K1) connects across the full-wave bridge rectifier (CR4), overcoming these obstacles. When the relay is de-energized, its contacts provide permanent magnet generator (PMG) voltage to the exciter field. When generator voltage is 90 volts line to line, voltage across CR4 energizes control relay (K1), removing the self-excited field circuit. The voltage regulator then supplies the exciter field. The absence of phase shift and fast response characteristics of transistor-type amplifiers eliminates feedback net- works and stabilizing transformers in this voltage regulator. Varying the output current to the exciter field varies the width of the square wave impulses. Figure 2-4 shows a pulse width modulation diagram. As the voltage rises (shown by the dotted back-to-back sawtooth), the square wave pulse to the exciter field is off longer than it is on. This causes the output of the ac generator to decrease. The decrease in voltage causes the back-to-back sawtooth to drop to its normal value (shown by the solid waveform). This causes the on and off times of the square wave pulse to the exciter field to be about equal. Varying the on and off excitation to the exciter field controls the ac generator output. AC GENERATOR FREQUENCY CONTROL Because of the fixed number of poles, the only means of fine-tuning the output frequency is controlling rotor rpm, often done by using CSDs. CSDs receive drive power from hydraulic power, pneumatic power, or the accessory drive section of an engine. It is for this reason that on most aircraft a CSD unit is located between the aircraft engine and the ac generator. On helicopters, the main generators are mounted on an accessory gearbox that is driven by the main transmission. The purpose of the CSD is to transfer and con- vert aircraft engine variable-speed rotation to a constant-speed rotation, which drives the generator. The CSD consists of a variable-displacement hydraulic pump, constant-displacement hydraulic motor, and a governing system. The governing system controls the rate of flow from the pump, thereby controlling the speed of the motor. There are several other components in the CSD that are necessary for self-regulating constant-speed operation. Among these components are three output-driven gear pumps: the charge pump, replenishing pump, and scavenge pump. A gear on the CSD output shaft drives these pumps, the limit governor, and basic governor. 2-5 AEf02004 OFF OFFON OFF OFFON ABOVE NORMAL 3-PHASE VOLTAGE NORMAL OUTPUT 3-PHASE VOLTAGE SQUARE WAVE SIGNAL TO EXCITER FIELD 18V ZENER REF Figure 2-4.—Pulse width modulation diagram.
p. 36
The pump wobbler and the pump section of the cylinder block assembly form the variable displace- ment pump in the CSD. Figure 2-5 shows a simplified CSD functional diagram. The pump wobbler consists of an outer stationary shell and an inner race. The inner race is separated from the wobbler shell by bearing rollers. It is free to turn with the pump pistons, which are always in contact with the race during operation. Two control pistons in the CSD housing move the wobbler sideways to vary the output of the pump. The CSD functions in three different phases of operation: overdrive phase, straight-through phase, and underdrive phase. When the engine input rpm is less than the rpm required for the generator, the CSD makes up the difference in rpm. The CSD does this by causing the pump wobbler system to respond to governor signals. This response causes the pump to supply more oil to the motor. The difference between the input and output rpm depends on the quantity of oil pumped by regulating the wobbler pump. Anytime the motor wobbler (output) is rotating faster than the cylinder block assembly (input) the CSD is in overdrive. When the input rpm equals the required output rpm, the rotary motion transmits through the CSD without hydraulic action. The pump wobbler would, theoretically, be positioned through the action of the governor to be concentric with the cylinder block assembly. In this condition, the pump neither sends oil to the motor nor accepts oil from the motor. The motor pistons lock in position against the motor wobbler, forcing the wobbler to rotate at the same speed as the cylinder block assembly. Since the drive starts in underdrive and operates normally in overdrive, this straight-through condition is only temporary. When engine input rpm exceeds the output rpm requirements for the generator, the CSD acts to subtract from the input rotation. The wobbler pump accomplishes this in response to the governor signal. The pump-motor action for underdrive is the reverse of the action required for overdrive. In the under- drive phase, the pump performs in a negative pumping action. The generator load opposes the driving force of the CSD, so it always tries to slow the wobbler. The cylinder block assembly then rotates faster than the motor wobbler. Excess input torque is dissipated in the reverse pumping action to the charged oil system. Whenever the motor wobbler is rotating more slowly than the cylinder block assembly, the CSD is in underdrive. When the engine overspeeds or if the basic governor fails, the CSD goes into underdrive to protect the generator from overspeed. The underspeed pressure switch in the governor oil line functions to break the electrical circuit of the ac control system. The system is protected during an underspeed condition. In some CSDs, aircraft engine oil from the engine lubricating system is the hydraulic medium. In this case, the CSD also functions as a pump for supplying the generator with engine oil for cooling. Due to cooling capabilities, oil-cooled generators are of smaller construction than air-cooled generators having a similar rating. Q2-1. What is the most common method of voltage regulation for ac generators? Q2-2. Why would we use a permanent magnet on the generator rotor in place of exciter windings? Q2-3. What happens when magnetic fields of alternating polarity pass across the armature windings? Q2-4. What controls the voltage induced into the armature windings? Q2-5. What must ac generator control systems protect against? Q2-6. What is the purpose of the rotating three-phase rectifier in a brushless genera- tor? Q2-7. What is the chief advantage of having dc exciter units integrated into ac generators? Q2-8. What is the only moving mechanical part in a solid state voltage regulator? 2-6
p. 37
Q2-9. What happens if the output of the control amplifier section of a voltage regulator is too low? Q2-10. In a solid-state voltage regulator, what com- ponent supplies the power to the bridge circuit? Q2-11. What prevents the generator from receiving excitation voltages when the frequency is too low? Q2-12. Why is controlling the rotor rpm the only means of fine-tuning the output frequency of a generator? Q2-13. What two components are joined by the CSD? Q2-14. List the components of the CSD. Q2-15 When the input engine rpm is too low, what happens to the CSD hydraulic pump? Q2-16. How is the CSD/generator system protected during underspeed conditions? CIRCUIT PROTECTION LEARNING OBJECTIVES : recognize ac circuit protection. Describe underfrequency and overfrequency control. Describe over- voltage and undervoltage control. Describe the feeder fault system. The generator and equipment and systems the generator powers need protection if a malfunction occurs. Circuits designed to sense malfunctions and energize relays provide protection by either warning the pilot of the malfunction or disconnecting the generator. The circuit protection needed and the methods used to control the malfunctions depend on aircraft and equipment design. For example, in a single-pilot aircraft, all malfunction detection and correction might be automatic. In a multi-piloted aircraft, the generating system may only warn the flight crew of a problem. This leaves corrective action to the discretion of the pilot in command. 2-7 PUMP WOBBLER PUMP CYLINDER BLOCK CLOSE-FITTING CENTER PLATE OR BLOCK MOTOR CYLINDER BLOCK OUTER RACE (STATIONARY) MOTOR ECCENTRIC OUTPUT MOTOR PISTON (EXTENDING) MOTOR MOTOR VALVE PLATE PUMP VALVE PLATE PUMP PISTON (DEPRESSED) PUMP WORKING PRESSURE CHARGE PRESSURE INPUT AEf02005 Figure 2-5.—Simplified CSD functional diagram.
p. 38
A supervisory panel (fig. 2-6) provides regulation and circuit protection for both the operating generator and equipment it powers in newer generating systems. This single component provides the same functions as several components in older power generating systems. The supervisory panel provides voltage regulation at 120/208 volts ac, while some types of CSDs provide frequency control at 400 hertz (Hz). The supervisory panel further has relays and other associated circuitry to disconnect the generator from the load if any of the following conditions occur: • Underfrequency • Overfrequency • Undervoltage • Overvoltage • Feeder fault (A condition where the current leaving the generator does not pass through the load. System design has cut out the need for feeder fault protection in systems where it is not likely to occur.) UNDERFREQUENCY AND OVERFREQUENCY CONTROL You should refer to figure 2-6 as you read this section. The PMG output is 39 volts at 600 Hz when the generator is on speed. The voltage reference bridge and the frequency sensitive bridge sample output voltage and frequency. The band-pass filter is tuned to 600 Hz (called its resonant frequency). Its minimum resistance and maximum current flow occur at 600 Hz. At this frequency, the output of the bridge networks are equal and opposite. The underfrequency/overfrequency sensor senses an on-frequency condition energizing the underfrequency/overfrequency relay (K1). Current flows through contacts 4 and 6 of energized relay K1. This allows generator control relay (K2) to energize if the frequency remains within tolerance for at least 3 seconds. If the PMG frequency changes from the desired 600 Hz, the band-pass resistance increases, and output of the circuits is unbalanced. The underfrequency/overfrequency sensor senses the un- balance and causes K1 to de-energize and immediately cuts off SCR-1. K2 de-energizes and disconnects any input to the exciter stator coils and reduces the generator output voltage to zero. Contacts 1 and 2 of K1 change frequency tolerance from 600 Hz ± 42 to 600 Hz ± 53 by adding resistance to the voltage reference bridge circuit when K1 energizes. This prevents the relay from chattering when the generator is operating at or very near its tolerance limit. VOLTAGE CONTROL A voltage regulating circuit changes PMG ac voltage to dc voltage and controls its amplitude. The voltage regulator senses all three phases of the generator output. If the average of these voltages is low, dc voltage to the exciter stator coils increases until output voltage is at the desired level. If output voltage is high, the voltage regulator decreases its output to the exciter stator coils until voltage is within tolerance. The generator system maintains three-phase output voltage to 120 volts ± 2 through a wide range of loads from 1 to 120 kilovolt amperes (kV A). One phase load may be one-third more than the other two phase loads, and voltage will not vary more than 5 volts between phases. It takes 1.7 amperes of current through the exciter stator coils to produce the desired magnetic field to generate a 120-/208-volt, 60-kV A load. Undervoltage Refer to figure 2-6 as you read this section. The undervoltage sensing and control circuit allows gen- erator output to power the distribution system when voltage rises to 105 volts during initial generator buildup. However, it does not de-energize the generator output until one or more phases falls below 90 volts. The undervoltage sensor monitors generator output. In conjunction with K1, it also energizes auxiliary control relay (K3), connecting generator output to the power distribution system. When K3 energizes, its contacts arm a timing cir- cuit that acts automatically when one or more phases are 90 volts or less. The timing cycle duration is elec- tronically divided into a 3-second period and a 1-second period: these two periods are additive. The total time involved before an undervoltage trip occurs is about 4 seconds. The delay circuitry allows time for corrective measures (circuit breakers or current limiters to open) to remove the cause of the undervoltage. If the cause of the undervoltage is removed and voltage rises to 105 volts before the initial time delay lapses, the generator stays on line. This cancels the lapsed increment and the full 4-second delay is reinstated. However, after a 4-second delay, differential protection latch-out relay (K6) energizes, energizing lockout relay (K4), and removes power from K3 and K2. 2-8
p. 39
2-9 PMG MOTOR EXCITER ROTOR ROTATING FIELD FAN PMG STATOR EXCITER STATOR ROTATING RECTIFIERS OUTPUT STATOR ROTATING ASSEMBLY PERMANENT MAGNET GENERATOR (PMG) ROTOR PMG STATOR COILS EXCITER STATOR COILS OUTPUT STATOR COILS BUS FEEDERS K1 K2 K3 K4 K5 K6 K7 UNDER/OVER FREQUENCY RELAY GENERATOR CONTROL RELAY AUXILIARY CONTROL RELAY LOCKOUT RELAY UNDERVOLTAGE LOCKOUT RELAY DIFFERENTIAL PROTECTION LATCH OUT RELAY DIFFERENTIAL PROTECTION RELAY ROTATING FIELD COILS EXCITER ROTOR COILS FEEDER FAULT (DIFFERENTIAL PROTECTION) CURRENT TRANSFORMER FEEDER FAULT (DIFFERENTIAL PROTECTION) CURRENT TRANSFORMER (MOUNTED ON GENERATOR CASE) R2 FEEDER FAULT SENSOR VOLTAGE REGULATOR/ SUPERVISORY PANEL BAND PASS FILTER VOLTAGE REFERENCE BRIDGE FREQUENCY SENSITIVE BRIDGE UNDER/ OVER FREQUENCY SENSORPOWER SUPPLY VOLTAGE REGULATOR 3-SEC TIME DELAY 3-SEC TIME DELAY 1-SEC TIME DELAY VOLTAGE REGULATING CIRCUIT UNDERVOLTAGE SENSOR 1 4 2 3 5 6 K1 ACR CONTROL OVERVOLTAGE SENSOR TIME DELAY K3 K2 SCR1DC TRANSISTOR POWER R1 SCR2 K4 K5 K6 K7 G Y DISTRIBUTION CENTER GEN. OF LIGHT 28V DC BUS SIGNAL LIGHTS GEN. CONT. BUS CONT. RESET ON OFF GEN. CONTROL SWITCH BUS MONITORING SWITCH ON OFF 1 3 2 4 6 5 AEf02006 28 VOLTS DC Figure 2-6.—Generator control system voltage regulator/supervisory panel.
p. 40
An excessive load on the generator can cause an undervoltage (a short circuit in a system that has a defective circuit breaker or fuse). This condition, if allowed to continue, could cause a fire or destroy the generator. Therefore, both K6 and K4 have holding circuits to keep them energized even when the undervoltage condition is corrected. To check for correction of the undervoltage, use the following procedure: 1. Place the GEN CONTROL SWITCH to the OFF position. 2. Pull and reset the GEN CONT circuit breaker. 3. Return the GEN CONTROL SWITCH to ON. Overvoltage As you read this section, refer to figure 2-6. An overvoltage sensor senses line voltage above 129 volts and starts a time delay. When started, the delay times out for a time inversely proportional to the overvoltage. A voltage of 130 volts on a single phase may have a delay of 3 to 4 seconds. A large overvoltage on all three phases may have a delay of a few milliseconds. When the delay completes timing, it triggers SCR2 into con- duction and allows K4 to energize. An overvoltage occurs if a voltage regulator mal- functions or if a large load (several loads) is removed from the generator at once. The voltage regulator is not fast enough to react when the generator loses several loads quickly. That is, it is possible for an overvoltage to occur during normal operation of the generating system. K4, supplying its own holding circuit, prevents the generator from powering the load again. If you place the GEN CONTROL SWITCH to either the RESET or the OFF position and back to ON, the generator stays on line. This prevents a generating sys- tem with a malfunctioning voltage regulator from cycl- ing on and off. FEEDER FAULT SYSTEM A short occurring between the generator and distribution system could cause a fire because there are not any protective devices (such as circuit breakers and fuses). A feeder fault circuit (fig. 2-6) protects against this possibility. The generator armature winding (output) has current transformers on each side of each winding. One set of current transformers (on the grounded side) is as close to the armature windings as possible. The other set is as close to the distribution system (and its protective devices) as possible. The transformer’s connections are then made so the voltages produced cancel each other out. The input to the feeder fault sensor would then be nearly zero. A short to ground or phase to phase would place a voltage across R2, caus- ing the feeder fault sensor to energize differential protection relay (K7). K7 then acts to energize K6, K6 energizes K4, and K4 de-energizes K2 and K3. Since K7 remains energized by its own contacts using PMG voltage, the system cannot be reset until removal of PMG voltage by stopping the generator. Q2-17. What component provides circuit protection for an ac generator? Q2-18. A supervisory panel will disconnect the gen- erator from the load under what conditions? Q2-19. What is the required output frequency of the PMG? Q2-20. How many amperes are required through the exciter coil to generate a 120-/208-volt, 60-kilovolt ampere (kVA) load? Q2-21. During an undervoltage condition, at what voltage will the generator be dropped off line? Q2-22. At what voltage will the generator be dropped off line during an overvoltage condition? Q2-23. What is feeder fault? AIRCRAFT POWER DISTRIBUTION LEARNING OBJECTIVES : Identify the uses of electrical buses. Describe the purpose of power transfer contactors. Recognize air- craft power sources. Recognize ac and dc 2-10 GEN EMERG GEN CONTROL RELAY ATTITUDE INDICATOR IFF PITOT HEATER RADAR ALTIMETER PRESSURIZATION 0 0 0BA C FLIGHT ESSENTIAL AC BUS AEf02007 Figure 2-7.—Three-phase ac bus.
p. 41
power distribution. Explain the operation of external power applied to an aircraft. Explain the operation of main generators applied to an aircraft. Recognize the component failures of ac/dc power distribution. Explain the operation of the emergency generator system. Identify grounded and ungrounded systems. Identify single-phase and polyphase systems. You have learned that various sources are used to provide electrical power to operate aircraft electrical equipment and systems. In this section, the system that connects the electrical power source to the equipment is discussed. Each manufacturer develops a system that meets the needs of their particular aircraft design. A system of priorities ensures certain critical equipment is operable if there is a malfunction. For example, if a power lead used to start an engine shorted out during flight, it is inappropriate to sacrifice all electrical power, especially power to lighting, navigation equipment, flight instruments, and other essential equipment. Therefore, systems of like priority are on a common line called a bus. ELECTRICAL BUSES Each type of aircraft has a group of buses identified by the priority of the equipment it powers. For example, a flight-essential bus may power emergency lighting, critical flight and engine instruments, and/or an emergency radio. Less important critical equipment receives power from an essential bus. Normal systems used to complete the assigned mission or provide crew comfort are on the main bus. The input to a bus may be either dc or ac. The output from the bus has a protective device such as a circuit breaker, fuse, or current limiter. A three-phase ac bus has three separate common lines, one for each phase (fig. 2-7). Sometimes, schematics show three phases drawn as one line. The P-3C aircraft is an example of versatility and flexibility in electric systems. Figure 2-8 shows a por- tion of the P-3C power distribution system. 2-11 XFR RELAY N O2(M NL C) MAIN AC BUS A ( 3-PHASE)(M NL C) ESSENTIAL BUS (M NL C) MAIN AC BUS A POWER TIME ON INDICATOR ( MN LC ) FLIGHT ESSENTIAL AC BUS ( FWD LC ) RUN AROUND RELAY NO 2 (M NL C) ESSENTIAL AC BUS RELAY NO. 2 (M NL C) FLIGHT ESSENTIAL AC BUS ( 3 - PHASE ) ( FWD LC ) INST BUS XFMR NO. 2 (FWD LC ) PHASE B 26 VOLT AC INSTRUMENT BUS NO. 2 (FWD LC ) 26 VOLT AC INSTRUMENT BUS NO. 1 ( FWD LC ) 28 VOLT AC FWD LIGHTING BUS (FWD LC ) INST BUS XFMR NO. 1 (FWD LC ) PHASE B INSTR AC BUS NO 2 TRANSFORMER ( FWD LC ) INSTR AC BUS NO 1 TRANSFORMER ( FWD LC ) FWD LIGHTING TRANSFORMER ( FWD LC ) FWD LTG BUS XFMR ( FWD LC ) PHASE B MONITORABLE ESSENTIAL A CB U S(3- PHASE )( FWD LC ) START ESSENTIAL AC BUS ( PHASE A )( FWD LC ) AFT LTG BUS X F M R(M NL C) PHASE B MAIN AC BUS B ( 3 - PHASE )( MN LC ) AFT LIGHTING TRANSFORMER ( FWD LC ) PROP DE - ICE TEST ( FWD LC ) 11 VOLT SUPPLY FOR PROP DE - ICE TEST 28 VOLT AC AFT LIGHTING BUS ( FWD LC ) INVERTER RELAY ( FWD LC ) ( FWD LC ) START ESSENTIAL AC BUS INVERTER (M NL C) ESSENTIAL AC BUS MONITOR RELAY ( MN LC ) OFF ON ESSENTIAL BUS MONITOR SWITCH ( R INBD OVHD PNL ) XFR RELAY N O .3(M NL C) ESSENTIAL AC BUS RELAY NO. 1 (M NL C) PHASE A MONITORABLE ESS AC BUS ( FWD LC )( TYPICAL ) ( TYPICAL ) 1 2 2 1 HEAVY DARK LINES INDICATE 3 - PHASE CIRCUTS THIN LINES INDICATE SINGLE PHASE AC OR DC CIRCUITS NOTE AEf02008 Figure 2-8.—Simplified P-3C electrical power distribution.
p. 42
2-12 5 13 17 20 16 4 3 AEt02001 Table 2-1.—F-14 Ac Bus Distribution
p. 43
Operation of the P-3C electrical power distribution system during normal flight conditions is entirely automatic. The crew only monitors the control panels for any indication of a malfunction. Control of the system is also automatic during ground operation, except switching to and from external power. Tables 2-1 and 2-2 list systems receiving power from the F-14 aircraft power distribution system. Many of these systems are not applicable to other naval aircraft. Often, systems vary with the model number of the same type of aircraft, and it isn’t appropriate to have the same bus system in all aircraft types or models. POWER TRANSFER CONTACTORS/RELAYS Naval aircraft power requirements have grown with technology, resulting in numerous power resources, which use transfer relays for distribution. There are basically two types of power transfer contactors: single coil and double coil. A single coil contactor consists of auxiliary contacts and two sets of three main contacts with a paralleled common output. The auxiliary contacts normally control identification lights on the power control panel. The two sets of three main contacts are arranged so that only one set of contacts can be closed at a time. A double coil relay is a two-section mechanically interlocking device having two energizing coils. Each section has three main contacts in addition to a common output. The mechanical interlock prevents simulta- neous actuation of the two relay sections. The auxiliary contacts normally control identification lights on the power control panel. POWER SOURCES This section contains a discussion of a representa- tive power distribution system used in F-14 aircraft. Electrical power is provided to the buses from four sources: • Left main generator • Right main generator • External power • Emergency power Two engine-driven generator transmissions supply ac. Each one is coupled to a 115-/208-volt ac, 400-Hz, three-phase brushless ac generator. These generators supply electrical power to the main, essential, and monitor ac buses. Either of the two generators can supply the entire electrical demand of the aircraft in the event one generator fails. Two transformer-rectifiers (TR) supply dc power. Each TR unit receives power from its respective main ac bus. The TR units convert 115 Vac to 28 Vdc for distribution to the secondary bus system. Either of the TRs is capable of supplying the entire dc requirements of the aircraft. A hydraulically driven, 5-kV A/50-amp generator provides ac and dc emergency power for essential equipment only. The emergency generator auto- matically actuates upon multiple generator or multiple TR unit failure. Emergency generator operation terminates upon reactivation of either main generator. The aircraft receives external power through an external ac power contactor. Discussion of each of these power sources, as well as contactor control logic, is contained in the following paragraphs. AC BUS DISTRIBUTION SYSTEM The distribution system consists of five three-phase ac buses, which are listed below: • Left main ac bus • Right main ac bus • Monitor ac bus • Ac essential number one bus • Ac essential number two bus The left and right main ac buses provide power to nonessential equipment throughout the aircraft. The monitor ac bus currently has no load attached to it. When used, it provides power to nonessential equipment only. With both generators operating, ac essential buses number one and number two and the 115-volt ac instrument bus power safety-of-flight equipment. The main generators normally supply power to these two buses, but they also tie in to the emergency generator when it is in operation. A step-down transformer supplies 26 Vac for instruments and navigation systems. The output of the transformer also provides power to safety-of-flight equipment. DC BUS DISTRIBUTION SYSTEM The main sources of dc power are the left and right TR units. These units receive power from the left and right main ac, three-phase buses, respectively. The left and right main dc buses provide power to nonessential dc systems. When both generators are operating, the 2-13
p. 44
2-14 9 16 1 12 14 6 4 12 14 8 5 19 18 7 10 11 20 AEt02002 Table 2-2.—F-14 Dc Bus Distribution
Table 2-2.—F-14 Dc Bus Distribution
DC ESSENTIAL NO. 1 BUS—28 V AC
L AICS RAMPS STOW R AICS RAMP STOW AWG-15 DC ALT LOW WARN DC ESS NO. 1 FDR MASTER ARM ARC-159 NO. 1 EMERG FLT HYD AUTO EMERG FLT HYD MAN STA 1 REL PWR A STA 1 REL PWR B L FIRE EXT △ R FIRE EXT △ ECM DEST △ STA 2, 3 & 4 REL PWR A STA 2, 3, & 4 REL PWR B ACM PWL PWR STA 1 AIM-9 REL PWR STA 8 AIM-9 REL PWR ARC-159 NO. 2 STA 5, 6 & 7 REL PWR A STA 5, 6 & 7 REL PWR B STA 8 REL PWR A STA 8 REL PWR B JETT 1 JETT 2 APX-72 DC UHF CONTR MLG SAFETY RLY NO. 1 MLG SAFETY RLY NO. 2 ICS PILOT △ ICS NFO △ R MID CPRSN BYPASS △ △ L MID CPRSN BYPASS △ ENG STALL TONE △ A/S INB/BARO ALTM DC △ BARO ALTM DC △ L FIRE DET/LT △ △ R FIRE DET/LT
INTERRUPTION FREE DC BUS—28 V DC
AUTO THROT DC INTEG TRIM DC
DC ESSENTIAL NO. 2 BUS—28 V DC
ENG/PROBE/ANTI-ICE FLT CONTR AUTH DC FLAP/SLAT CONTR SHUT-OFF MACH TRIM DC AIR SOURCE CONTR NOSE WHEEL STEER/AFCS SPD BK P-ROLL TRIM ENABLE FUEL P/MOTIVE FLOW ISOL V ENG START FUEL FEED/DUMP FUEL MGT PNL ENG ANTILCE VALVES NLG STRUT LCH RAR ADVSY DC ESS NO. 2 BUS FDR CABIN PRESS DISPLAY PWR AFCS BUS FDR △ UHF NO. 2 △ ALPHA COMP/PEDAL SHAKER △ ILS ALR 61 FC CAN/LAD CAUTION/EJECT CMD IND RAIN RPL/ANTI-ICE CONTR/HK CONTROL
DC ESSENTIAL NO. 2 BUS—28 V DC—CONTINUED
ANN PANEL PWR TILT/EJT-28 AN/ARA 50/ARA-69 △ AN/ARA-50 △ CSDC ECS TEMP CONTR DC FUEL QTY IND DC OVSP CAUTION R OIL HOT END OIL COOL TACAN/BDHI APN 154 HYD PRESS IND HYD VALVE CONTR FUEL TRANS ORIDE ANGLE ATK IND DC EMERG GEN TEST AICS LKUP PWR EMERG GEN XFMR LKUP PWR HYD PUMP SPOILER CONTR FUEL VENT VALVE STARTER CONTR VALVE △ FUEL LOW CAUTION OXY-BINGO CAUTION L GEN CAUTION R GEN CAUTION TR-ADVSY/PLT ANN PNL AUX PWR BLEED AIR/L OIL HOT FUEL PRESS AUTO EXT L CONTR INBD SPOILER CONTR MACH LEVER SHIFT L DC TEST/RUDDER TRIM WHEELS POS IND MLG HANDLE RLY NO. 1 MLG HANDLE RLY NO. 2 AUX FLAP/FLAP CONTR WING POS IND DC GND ROLL BRAKING/SPOILING POS IND
AFCS BUS—28 V DC
YAW SAS A YAW SAS B YAW SAS M PITCH COMPTR DC ROLL CMPTR DC
DC LEFT MAIN BUS—28 V DC
RECON ECS CONT DC RECON POD CONT RECON POD DC PWR NO. 1 RECON POD DC PWR NO. 2
DC RIGHT MAIN BUS—28 V DC
STA 8 AIM-9 COOL PWR STA 8B AIM-9 PWR STA 8A AIM-9 PWR STA 1 AIM-9 COOL PWR STA 1B AIM-9 PWR STA 1A AIM-9 PWR DYHR UNIT R TGT TEST/ACM BIT COUNTING ACCEL MONITOR BUS CONTR GND TEST/MARCH LV BIT MID CPRSN BYPASS PWR DDI/ANN PNL DIM CONTR GUN ARMED POWER OUTBD SPOILER CONTR INTRPT FREE DC BUSS FDR NO. 2 WSHLD DEFOG CONTR GUN CLR/GUN CONTR PWR DC LIQUID COOLING CONTR DC ALE-39 SEQ 1 & 2 SQUIBS ALE-39 CHAFF/FLARE DISP
AEt02002
2-14
p. 45
monitor bus provides power to nonessential equipment only. The automatic flight control system (AFCS) bus and essential buses numbers one and two provide power to safety-of-flight equipment. The TR units normally supply these three buses, but they receive power directly from the emergency generator when it is in operation. Either external electrical power or both generators can supply the entire ac and dc bus system. If only one generator is operating, the entire ac and dc bus systems (except the monitor ac and dc buses) have power. If only one TR unit is in operation, the entire dc bus system (except the monitor bus) has power. The emergency generator powers only the ac-essential bus, 115-volt ac instrument bus, 26-volt ac instrument bus, dc essential bus, and AFCS buses. If a complete propulsion system fails, the hydraulic pressure developed by the windmilling of the engines is sufficient to drive the emergency generator. In this configuration, only the essential ac number one bus and the dc essential number one bus have power. Tables 2-1 and 2-2 list the elements of the various ac and dc buses and the applicable systems attached to each particular bus. Q2-24. In an electrical system, what is a “bus?” Q2-25. How are buses identified? Q2-26. What are the types of output protection de- vices used by buses? Q2-27. What are the two basic types of power con- tactors? Q2-28. What are the four power sources available to the F-14 aircraft? Q2-29. List the three-phase buses of the F-14 air- craft. Q2-30. What dc bus will NOT be powered in the event of one TR failure in the F-14 aircraft? AC/DC POWER DISTRIBUTION OPERATION As you have already learned, the two main generators and two TR units of an external ac power source provide electrical power. If engines are operating and hydraulic pressure is available, the emergency generator is available as a source of power. Switching between power supply systems is automatic without pilot action. However, the pilot can selectively isolate power sources and the distribution system in emergency situations. When operating normally, the buses receive power through a series of contacts and logic situations, depending on the power source(s) in use. Normal power sources include external power and the left and right generators. Grounded and ungrounded, single-phase and polyphase systems also are discussed. External Power The external electrical power system (fig. 2-9) permits application of three-phase, ac power to the aircraft electrical power distribution system. External power goes to the ground power monitor (GPM) and de-energized contacts of the external power contactor. 2-15 1 2 3 1 2 3 1 2 3 SENSING LOGIC TXMFR RECTFR TRIP LOGIC 28 VDC GROUND POWER MONITOR 30 PWR LEFT GEN. L. MAIN BUS MAIN POWER CONTACTOR K2 RIGHT GEN. MAIN POWER CONTACTOR K1 EXTERNAL POWER CONTACTOR EXTERNAL POWER PANEL A B C F E N PINS E AND F ARE JUMPERED IN EXTERNAL PLUG RESET SWITCH AEf02009 R. MAIN BUS Figure 2-9.—External ac power functional block diagram.
p. 46
The GPM prevents application of external power not within tolerances. If an undervoltage, overvoltage, underfrequency, overfrequency, or a phase reversal fault occurs, the GPM disconnects external power from the power distribution system. When all the power parameters are within tolerance, the GPM relay energizes, supplying 28 Vdc from the GPM transformer-rectifier to pin F of the external power panel. NOTE: Pins E and F are jumpered in the external power plug. The power then runs through pin E and energizes the external power contactor. Three-phase power at pin one of the external power contactor then runs to the left main ac bus and right main ac bus through their respective contactors. Power from the left main ac bus (fig. 2-10) goes to the left TR unit. It also goes through the de-energized contacts of both ac essential power transfer relays to all essential ac buses and to the 26-volt ac transformer. This transformer, in turn, feeds power to the 26 Vac instrument and navigational buses. The right main ac bus supplies power to the right TR unit. Both left and right TR units (fig. 2-11) provide power to all dc buses through their respective power contactors and power transfer relays. External electrical power is automatically inhibited from some systems when external air conditioning is not being supplied to the aircraft. After aircraft engines start and the left generator comes on line, the left main contactor automatically disconnects external power. Some aircraft have a light on the caution/advisory panel that is illuminated by a switch, mounted on the external power receptacle, when the door is open. However, there is no cockpit indication of external power application. The only con- trol the pilot has over external power being applied or removed is the hand signals between the pilot and the plane captain. Main Generators Refer to figure 2-10 as you read. With external power connected and engine start initiated, the left generator comes on line when all parameters are within tolerance. With the left generator on line, the left main ac power contactor energizes. The left generator now supplies power through the left main ac power con- tactor (K1) pins one and two to the left and right main ac buses. These two buses, in turn, provide power to both TR units, all other 115-volt ac buses, and the 26-volt ac transformer. The TR units and the 26-volt ac transformer provide power to all other respective buses. 2-16 115 VAC LEFT MAIN AC BUS (30) MASTER GEN LR NORM NORM TEST OFF/ RESET OFF/ RESET LEFT ENGINE L MAIN AC POWER CONTACTOR K1 LEFT GENERATOR CONTROL UNIT RIGHT GENERATOR CONTROL UNIT L GEN R GEN EMERG FIELD EXCITATION FIELD EXCITATION OUTPUT OUTPUT TRANS- MISSION AC GENERATOR RIGHT ENGINE TRANS- MISSION AC GENERATOR LEFT GENERATOR TRANSMISSION ENERGIZED WHEN LEFT GENERATOR IS ON ENERGIZED WHEN RIGHT GENERATOR IS ON ENERGIZED WHEN EXTERNAL POWER IS ON 12 3 LEGEND 115 VAC POWER 26 VAC POWER 28 VDC POWER CONTROL AND SIGNAL POWER EXTERNAL AC POWER CONTACTOR R MAIN AC POWER CONTACTOR K2 K3 1 1 12 2 2 3 3 3 1 2 3 RIGHT GENERATOR TRANSMISSION L MAIN XFMR/RECT S MAIN XFMR/RECT (30) 115 VAC ESSENTIAL AC NO.2 BUS PH A PH C PH B 26 VAC BUS FDR INST BUS FDR AC ESS BUS NO. 2 FDR PHA AC ESS BUS NO. 2 FDR PHC AC ESS BUS NO. 2 FDR PHB PILOT AC ESSENTIAL CB PANEL 2 1 115 VAC MONITOR AC BUS (30) (NO LOADS) 115 VAC REMAIN AC BUS (30) AC ESSENTIAL POWER TRANSFER NO. 2 RELAY K3 NORMALLY DEENERGIZED ENERGIZED WHEN EMERGENCY GEN IS ON AND OUTPUT IS REGULATED NO. 1 BUS PH A AC ESSENTIAL POWER TRANSFER NO.1 RELAY K2 115 VAC ESSENTIAL AC 115 VAC ESSENTIAL AC NO.1 BUS PH C 115 VAC ESSENTIAL AC NO.1 BUS PH B 26 VAC NAVIGATION BUS 26 VAC TRANS- FORMER MLG SAFETY J RELAY K17 26 VAC INSTRUMENT BUS ENERGIZED WHEN EXTERNAL POWER IS ON OR WHEN BOTH GENERATORS ARE ON NORMALLY DEENERGIZED ENERGIZED WHEN EMERG. GEN IS ON B2 B3 2 3 115 VAC B1 INST S6 INST BUS FDR ESSENTIAL AC NO. 1 BUS PH B AC MONITOR BUS RELAY K1 3 21 115 VAC INSTRUMENT BUS PHB AEf02010 Figure 2-10.—Simplified ac power distribution schematic.
p. 47
When the left main contactor energizes, it removes external power from the aircraft bus system. The external power unit is now shut down and cable removal may be done safely. With the right generator on line, the right main contactor energizes, allowing the right generator to power the right main bus. The energized contacts of the right main ac power contactor (K2) prevent the left generator from powering the right main bus. Likewise, the energized left main contactor prevents the right generator from applying power to the left main bus. When both generators are operating, the left gen- erator powers the left main bus. The left main bus powers all 115-volt ac essential and instrument buses through the ac essential power transfer relays and through the 26-volt ac transformer. The transformer powers the instrument and navigation buses. The left TR unit (fig. 2-11) receives power from the left main bus. It provides power to the left main dc bus through contact Al of the energized left main dc power contactor. The left main dc bus provides power to the essential dc buses through the contacts of de-energized dc essential power transfer relays. In addition, the left main dc bus powers the interruption-free dc bus. This bus, in turn, powers the 28-volt dc AFCS bus through the energized autopilot power transfer relay. The right generator provides power to the right main bus, which through the ac monitor bus relay powers the monitor ac bus. The 28-volt dc right main bus receives power from the TR unit through the energized contacts of the right main dc power contactor. The right main dc bus energizes the monitor dc bus through the dc monitor bus relay. It also energizes the 28-volt dc interruption-free bus. Because the interruption-free bus receives power from both TR units, the bus is not affected by a loss of either main generator or either TR unit. Component Failures The power distribution system design ensures power is available to operate all aircraft equipment. This includes all equipment essential to accomplish the assigned mission and ensure safety of flight. If a component or engine should fail, power must be available for continued safe operation. The distribution system design provides a continuous power source under all adverse conditions. As you know, either of the generators is capable of supplying the entire load of the 2-17 1. IF EITHER GENERATOR TRANSMISSION FAILS OR IS SHUT OFF THE ENTIRE AC LOAD IS AUTOMATICALLY TRANSFERRED TO THE OPERATING GENERATOR. 2. IF EITHER TRANSFORMER RECTIFIER FAILS THE ENTIRE DC LOAD IS AUTO- MATICALLY TRANSFERRED TO THE OPER- ATING TRANSFORMER RECTIFIER 3. IF BOTH GENERATORS OR BOTH TRANS- FORMER RECTIFIERS FAIL THE EMERG- GENCY GENERATOR AUTOMATICALLY SUPPLIES THE ESSENTIAL AC AND DC BUSES. NOTES 115 VAC LEFT MAIN AC BUS (30) L MAIN XFMR/RECT (30) R MAIN XFMR/RECT (30) 115 VAC REMAIN AC BUS (30) L MAIN DC POWER CONTACTOR K2 LEFT TRANS- FORMER RECTIFIER (100A) DC ESSENTIAL POWER TRANSFER NO. 1 RELAY K4 DC ESSENTIAL POWER TRANSFER NO. 2 RELAY K3 NORMALLY DEENERGIZED ENERGIZED WHEN EMERGENCY GENERATOR IS ON. NORMALLY DEENERGIZED ENERGIZED WHEN EMERGENCY GENERATOR IS REGULATED 1 1 1 2 2 2 3 3 3 RIGHT TRANS- FORMER RECTIFIER (100A) R MAIN DC POWER CONTACTOR K1 ENERGIZED BY RIGHT TRANSFORMER RECTIFIER OUTPUT A3 A2 A1 25 VDC RIGHT MAIN DC BUS 28 VDC LEFT MAIN DC BUS A3 A2 A1 ENERGIZED BY LEFT TRANSFORMER RECTIFIER OUTPUT 28 VDC AWG-9 DC BUS INTRPT FREE DC BUS FDR NO. 2 28 VDC INTRPT FREE DC BUS POWER FROM AWG-9 SYSTEM INTRPT FREE DC BUS FDR NO. 1 TRANS/RECT 28VDC AFCS BUS DC ESS NO.1 FDR PILOT DC ESSENTIAL CB PANEL DC ESS NO.2 FDR AUTOPILOT POWER TRANSFER RELAY K1 ENERGIZED WHEN EITHER MAIN DC BUS IS ENERGIZED A2 A3 A1 DC MONITOR BUS RELAY K5 28 VDC MONITOR DC BUS (NO LOADS) ENERGIZED WHEN EXTERNAL POWER IS ON WHEN BOTH GENERATORS ARE ON. AFCS BUS FDR 28VDC ESSENTIAL DC NO. 1 BUS 28 VDC ESSENTIAL DC NO. 2 BUS 1 DC ESSENTIAL N O .2C B PANEL AEf02011 Figure 2-11.—Simplified dc power distribution schematic.
p. 48
aircraft. Likewise, either of the TR units is able to supply the entire dc load. Adverse conditions that could occur in the aircraft’s electrical systems include the following: • Left generator failure • Right generator failure • Left TR unit failure • Right TR unit failure NOTE: The emergency generator will auto- matically come on line if both generators fail or if both TR units fail. The following paragraphs discuss each adverse condition. Refer to figures 2-10 and 2-11 as you read about each condition. LEFT GENERATOR FAILURE. —When the left generator drops off line, the left main ac power contactor de-energizes. The right generator now powers the left main ac bus through contacts three and two of the de-energized external ac power contactor. All other buses receive power except for the 115-volt ac and 28-volt dc monitor buses. Both generators must be operating for the monitor buses to receive power because of the action of the monitor bus relays. RIGHT GENERATOR FAILURE.—If the right generator or associated equipment should fail, the left generator supplies power to both main ac buses. Power goes to the right main ac bus through de-energized contacts three and two of the right main ac power contactor. Power for the other ac buses and the TR units is as previously described. LEFT TR UNIT FAILURE.—When the left TR unit fails, the left main dc power contactor de-energizes. Power then goes across de-energized contacts A3 to A2, powering the left main dc bus. The right TR unit also continues to power the right main dc bus. Power distribution to the remaining dc buses is normal operation, except for the dc monitor bus. To power the monitor bus, both TR units must be operating. This is because of the action of the dc monitor bus relay. RIGHT TR UNIT FAILURE. —When the right TR unit fails, the right main dc contactor de-energizes. Power from the left TR unit runs across de-energized contacts A3 to A2 of the right dc contactor. From here power goes to the right main dc bus, thus maintaining operation of the entire dc distribution system except for the loss of the monitor dc bus. As shown, the power distribution system maintains its integrity with a loss of either generator or TR unit. This ensures all systems are available for safe flight and mission accomplishment. 2-18 MASTER GEN LR NORM NORM TEST OFF/ RESET OFF/ RESET EMERG EMERGENCY GENERATOR CONTROL UNIT PILOT DC ESSENTIAL CB PANEL DC ESSENTIAL POWER TRANSFER N0. 1 RELAY K4 DC ESSENTIAL POWER TRANSFER N0. 2 RELAY K4 1 1 2 2 3 3 PH A PH C PH B 26 VAC BUS FOR INST BUS FDR AC ESS BUS NO. 2 FDR PH A AC ESS BUS NO. 2 FDR PH C AC ESS BUS NO. 2 FDR PH B PILOT AC ESSENTIAL CB PANEL 2 1 1 AC ESSENTIAL POWER TRANSFER NO. 2 RELAY K3 NO. 1 BUS PH A 115 VAC ESSENTIAL AC NO.1 BUS PH C 115 VAC ESSENTIAL AC 26 VAC NAVIGATION BUS 26 VAC TRANS- FORMER MLG SAFETY J RELAY K17 26 VAC INSTRUMENT BUS 115 VAC INSTRUMENT BUS PH B B2 B3 2 3 115 VAC B1 INST S6 INST BUS FOR ESSENTIAL AC NO. 1 BUS PH B 28 VDC ESSENTIAL DC NO.1 BUS 28 VDC ESSENTIAL DC NO.1 BUS AFCS BUS FDR DC ESSENTIAL NO.2 CB PANEL EMERGENCY GENERATOR SOLENOID CONTROL VALVE FROM COMBINED SYSTEM HYDRAULIC PRESSURE EMERGENCY GENERATOR GENERATOR DC AC HYDRAULIC MOTOR 1 2 3 1 2 3 1 2 3 NORMALLY DEENERGIZED ENERGIZED WHEN EMERGENCY GEN IS ON AND OUTPUT IS REGULATED NORMALLY DEENERGIZED ENERGIZED WHEN EMERG. GEN. IS ON 115 VAC ESSENTIAL AC NO. 2 BUS AC ESSENTIAL POWER TRANSFER NO.1 RELAY K2 NORMALLY DEENERGIZED ENERGIZED WHEN EMERG. GEN. IS ON AND OUTPUT IS REGULATED ENERGIZED WHEN EITHER. MAIN DC BUS IS ENERGIZED NORMALLY DEENERGIZED ENERGIZED WHEN EMERGENCY GENERATOR IS ON . AUTOPILOT POWER TRANSFER RELAY K1 28 VDC AFCS BUS NOTE ALL RELAYS SHOWN ENERGIZED AEf03012 Figure 2-12.—Emergency generator power distribution system.
p. 49
Emergency Generator Operation The emergency generator system (fig. 2-12) automatically activates when the left main dc bus loses power. The emergency generator solenoid de-energizes, activating the hydraulic motor that drives the emergency generator. The emergency generator provides ac and dc power to the essential bus circuits when normal power fails. The emergency system is completely self-sufficient and independent of the primary and secondary power sources. The emergency generator control unit monitors ac output and regulates the output at 115 volts. This voltage is available as long as the hydraulic motor is operating under full system pressure. If both engines flame out, the hydraulic pressure produced by windmilling engines cannot operate the hydraulic motor at optimum output. This causes the left and right generator outputs to drop below tolerance. The emergency generator control unit disconnects the essential ac and dc power transfer number two relays. Equipment on essential ac and dc number one buses must be capable of operating on below normal voltage in an emergency. When the emergency generator activates (both generators or both TR units failed), ac power routes through both transfer relays to essential ac buses. Dc power goes through the dc essential power transfer relays to the dc essential and AFCS buses. Not all ac and dc main and monitored buses receive power during emergency generator operation. If both engines fail, the windmilling effect drives the emergency generator below normal performance levels. The ac essential and dc essential power transfer number two relays now de-energize. Only the ac essential and dc essential number one buses receive power. This configuration enables the flight crew to jettison aircraft stores, communicate, and destroy classified equipment before taking emergency escape procedures. Grounded Systems The termgrounded systemmeans that one leg of the system connects to a common conductor. This common conductor can be the Earth, the skin of the aircraft, or a structural member of the aircraft. When the grounded leg of the circuit connects to a good electrical con- ductor, this conductor may serve as one leg of the circuit, cutting out the need for a separate conductor. Figure 2-13 shows a simple grounded system. Although the grounds are at different points, the potential at these points is the same since they connect to a common conductor. The letter N designates any wire that completes the equipment circuit to the ground network. Any wire designated as N may come in contact with ground at any point without causing the equipment to mal- function. Grounding three-wire systems can be done by grounding one of the phases, usually the B-phase in aircraft. Make sure you ground the same phase in all equipment. Figure 2-14 shows the grounded three-phase systems. In four-wire systems, the neutral is ground. The grounded circuit is better than the ungrounded one because it reduces overall weight by using fewer conductors. This results in a reduction in cost and space requirements. Other advantages are that trouble- shooting is simplified and the impedance of the ground return path is lower than that of a run conductor. A disadvantage of a grounded system is that short circuits result when a bare spot on any ungrounded conductor touches ground. Another disadvantage is having circuits of different potentials and frequencies use a common ground. There is a possibility of one circuit feeding into another. This problem often happens in electronic circuits. 2-19 AEf02013 A 6 Figure 2-13.—Grounded system. (A) (B) (C) AEf02014 Figure 2-14.—Grounded three-phased systems. (A) Grounded three-wire wye; (B) grounded four-wire wye; (C) grounded delta.
p. 50
Ungrounded Systems The term ungrounded system means that the circuit in no way connects to ground. All conductors run from the power source to the loads. Circuits of this type are often referred to as being above ground. The ungrounded system has one advantage—it prevents one circuit from feeding into another because the circuits are completely insulated from each other. The system has the disadvantage of adding more weight because it requires more conductors than the grounded system. This results in added cost and space requirements. Both the grounded and ungrounded systems are used for specific purposes in modern aircraft. Single-phase and Polyphase Systems Single-phase systems are of simple design and con- struction. They are used when there are relatively low power requirements. Polyphase systems are more complicated in construction and design. These systems are used when high power is required. These systems provide a smoother source of power. Single-phase power is available from polyphase systems. When doing this, the load on the polyphase system must be kept balanced. Q2-31. In an F-14 aircraft, what is the purpose of the GPM? Q2-32. How will the pilot of an F-14 know if external power is applied to or disconnected from his aircraft? Q2-33. What is the purpose for jumping pins E and F on the external power receptacle? Q2-34. In an F-14 aircraft, with both main genera- tors on line, which buses does the left main generator power? Q2-35. With both generators on line, 115-Vac es- sential bus number two fails to be powered. Which components could be faulty? Q2-36. External power is applied to the aircraft, the right generator comes on line, and only the main ac bus loses power. What component could be faulty? Q2-37. If the right TR fails, what bus, if any, will be lost? Q2-38. What will cause the monitor bus to lose power? Q2-39. What ac bus does the emergency generator supply power to? Q2-40. What is the main advantage of a grounded system? Q2-41. What are the disadvantages of ungrounded systems? 2-20